14.5 kVA, Single Phase, Standby Diesel Generator with Kubota Engine in Canopy, 400L Tank & Load Bank

Order Code: 421474

Print
Product Code
ED14.5KYE-400-LB
RRP: $23273.25 incl. GST

Request a Quote Now

Click the link below to connect with our team.
We’ll help you define the technical requirements for your Standby Generator.

Request Quote

Precision-Built. Performance-Tested. Fast Turnaround.

Welling & Crossley Generators are assembled and tested in our advanced Melbourne facility, ensuring each unit meets the performance and reliability standards demanded by Australian conditions.

With a typical 5–10 day turnaround, our local assembly allows for rapid delivery without compromising on quality. Submit a quote request today, and our technical team will assess your requirements to configure the most suitable product for your application.

Technical Specifications
Brand Welling & Crossley
Product Type Standby Generator
Fuel Diesel
Generator Type Single Phase
Generator Rating (kVA) 1 to 20kVA
Pack Weight (KG):
0.00
Description

The Welling & Crossley ED14.5KYE-400-LB 14.5kVA Single Phase Standby Diesel Generator is a complete diesel backup power solution designed for customers who need reliable single phase standby power, extended fuel capacity, and added protection against light-load running. Powered by a proven Kubota D1703-E2BG diesel engine and matched with a Crossley SLG series single bearing, 4-pole brushless alternator, this generator is built for dependable performance across residential, rural, commercial, workshop, and light industrial applications.

This model includes a large 400 litre bunded diesel fuel tank and an integrated load bank, making it especially practical for sites where the generator may operate for extended periods or where electrical load can vary. The load bank automatically applies artificial load when site demand is light, helping reduce the likelihood of engine glazing and supporting optimal engine performance.

Supplied as a fully integrated Welling & Crossley power generation system, the ED14.5KYE-400-LB comes complete with a remote start/stop control system, auto-start control module, weather protective acoustic canopy, and heavy duty fabricated steel base frame. The acoustic canopy helps protect the generator from the elements while reducing operating noise to approximately 73 dB(A) at 1 metre, or 65 dB(A) at 7 metres.

For safer diesel storage on site, the generator includes a fully bunded fuel tank compliant with AS 1940-2004, providing secondary containment designed to retain and recover spillage if required. Anti-vibration pads are fitted between the engine, alternator, and base frame to help isolate vibration and support smoother operation.

The standard auto-start control module supports local or remote starting and provides key monitoring and protection functions, including alternator frequency and speed sensing, generator/load power monitoring, accumulated power monitoring, generator overload protection, engine speed protection, run-time scheduling, battery voltage monitoring, and static battery charging. It can also be configured to operate with an Automatic Transfer Switch for automatic standby power applications.

With its Kubota diesel engine, 14.5kVA standby rating, 400L bunded tank, acoustic canopy, integrated load bank, and remote start capability, the ED14.5KYE-400-LB is a strong choice for customers needing reliable single phase diesel standby power with extended fuel capacity and added protection for light-load operation.


Starting is remote or local to the machine with a push Start/Stop button and includes
  • Alternator frequency & speed sensing
  • Fully configurable via the interface or PC using USB
  • Generator/load power monitoring
  • Accumulated power monitoring
  • Generator overload protection
  • Fuel and start outputs
  • Engine speed protection
  • Engine run-time scheduler
  • Battery voltage monitoring
  • Static battery charger
Features
Weather-protective Acoustic Canopy

A weather-protective acoustic enclosure is included to protect and prolong the life of your generator. Finished using a powder coat paint finish, this acoustic canopy will reduce the noise level of the generating set to approximately 70 dB(A) at 1 metre from the machine (63 dB(A) @ 7 m).


Heavy-duty fabricated steel base frame

The complete generating set is mounted as a whole onto a heavy-duty fabricated steel base frame. Anti-vibration pads are fixed between the engine and alternator feet and the base frame, ensuring complete vibration isolation of the rotating assembly.


Bunded Fuel Tank (AS 1940-2004 compliant)

The fuel tank is fully bunded and complies fully with relevant sections in AS 1940-2004. It has a secondary containment compound with a capacity as big or bigger than that of the tank, and is made of surface-coated steel. This compound is designed to sufficiently retain spillage and enable recovery of any spillage. For more information regarding AS 1940-2004 compliance, refer to the standard or contact us.


Battery Charger

This trickle charge battery charger ensures that your generator can start up when needed. It has both 12v and 24v charging capabilities.


Control Panel with Emergency Stop button

This control panel monitors the controls of a single unit to achieve automatic start/stop, data measuring/monitoring, alarm protection and three remote systems (remote control, remote measuring and remote communication). The controller adopts a large liquid crystal display (LCD) and has a 32-bit microprocessor with precision parameters for measuring, fixed value adjustment, time setting and threshold adjustment.


Prime or Standby Power

Standby: kVA @ 0.8 pf. These ratings are applicable for supplying continuous electrical power (at variable loads) in the event of a utility power failure. No overload is permitted on these ratings. Minimum output from alternators is peak continuous rated (as defined in 1SO 8528-3 @ 27°C. Annual hour limitation: 500 hours).

Prime (continuous): kVA @ 0.8 pf. (Divide standby rating by 1.1). Available for continuous electrical output. There is no hour limitation. 10% overload is available for 1 hour in 12. The generating set and this specification are designed for environmental conditions of up to 27°C, up to 152.4 m above sea level and up to 60% relative humidity. Ratings at 0.8 pf. For ratings outside this range, please contact us.


Alternator Specifications
Alternator Model Crossley
Electric Power Single Phase
Active Rating 14.5 kVA at 0.8 pf (Standby)
Power 11.6 kW
Voltage 240V
Frequency 50Hz

Engine Specifications
Engine Model Kubota D1703-E2BG
Engine Speed 1500 rpm
Cylinder No. 3
Cubic Capacity 1.647 L
Bore/Stroke 87 x 92.4 mm
Compression Ratio 17 : 1
Aspiration Natural
Starter Voltage 12V
Flywheel (Max Continuous Power) 14 kW
Combustion Air Flow 1.3 m³/min
Cooling Air Flow 48 m³/min
Cooling System Radiator Cooled
Heat Rejection to Cooling System 12.8kW
Exhaust Gas Flow 3.4 m³/min
Exhaust Gas Temperature 550°C
Fuel Type Diesel
Fuel Tank Capacity 400 L
Approx. Fuel Consumption (Continuous) 4.1 L/hr
Approx. Fuel Consumption (Standby) 4.67 L/hr

Generator Specifications
Dimensions (L x W x H) 2000 x 900 x 1580 mm
Weight 1180 kg
Product Range Brochure
Downloads
Product Information and Data Sheets
Download Product Information & Data Sheets v1.0